VoltageDroopControl
Package: PowerOperationsOpenAPIModels · Source: Operations/SupplementalAttributes/VoltageDroopControl.json
Supplemental attribute for a voltage droop controller (PSS/E voltage droop control): a set of generators jointly regulating the reactive power at one bus along a Q–V characteristic. While the controller is available its regulated bus and characteristic override each member’s own voltage target; while it is unavailable the members fall back to their own targets. Membership and each member’s relative reactive power weight are VoltageControlAssociation rows. The characteristic holds reactive_power_limits.max below voltage_limits.min, ramps to deadband_reactive_power at deadband_voltage_limits.min, holds it through deadband_voltage_limits.max, ramps to reactive_power_limits.min at voltage_limits.max, and holds it above.
Properties
| Property | Type | Required | Unit | Description |
|---|---|---|---|---|
id | integer | yes | — | Unique integer identifier for this supplemental attribute. |
name | string | yes | — | Name of the voltage droop controller. |
available | boolean | — | — | Whether the controller is in service (PSS/E STATUS). While false, members regulate their own targets. |
regulated_bus_id | integer | yes | — | ID of the bus whose reactive power the controller regulates; overrides every member’s own regulated bus while the controller is available. |
reactive_power_limits | MinMax | yes | MVAr | Reactive power held below voltage_limits.min (max, PSS/E QMAX) and above voltage_limits.max (min, PSS/E QMIN). Units: MVAr. |
deadband_reactive_power | number | yes | MVAr | Reactive power held while the regulated bus voltage is inside deadband_voltage_limits (PSS/E QDB). Must lie strictly between reactive_power_limits.min and reactive_power_limits.max. Units: MVAr. |
voltage_units | string (VoltageUnitBasis) | — | — | Unit basis for the voltage fields. COMPONENT_BASE (per-unit on the regulated bus base voltage) is PSS/E RAW native. |
deadband_voltage_limits | MinMax | yes | kV / pu (by voltage_units) | Voltage band inside which the controller holds deadband_reactive_power (PSS/E VDBLOW, VDBHIGH). Must lie inside voltage_limits. Units: per voltage_units — NATURAL_UNITS: kV, COMPONENT_BASE: pu . |
voltage_limits | MinMax | yes | kV / pu (by voltage_units) | Voltages at which the characteristic reaches reactive_power_limits.max (min, PSS/E VLOW) and reactive_power_limits.min (max, PSS/E VHIGH). Units: per voltage_units — NATURAL_UNITS: kV, COMPONENT_BASE: pu . |