ESST4B

Package: PowerDynamicsOpenAPIModels · Source: Dynamics/DynamicGeneratorComponent/AVR/ESST4B.json

In these excitation systems, voltage (and also current in compounded systems) is transformed to an appropriate level. Rectifiers, either controlled or non-controlled, provide the necessary direct current for the generator field. Parameters of IEEE Std 421.5 Type ST4B Excitacion System. ESST4B in PSSE and PSLF

Properties

Property Type Required Unit Description
Tr number yes — Regulator input filter time constant
id integer yes — Unique integer identifier for this component
K_pr number yes — Regulator proportional gain
K_ir number yes — Regulator integral gain
Vr_lim MinMax yes — Voltage regulator limits
Ta number yes — Voltage regulator time constant
K_pm number yes — Voltage regulator proportional gain output
K_im number yes — Voltage regulator integral gain output
Vm_lim MinMax yes — Limits for inner loop output
Kg number yes — Feedback gain constant of the inner loop field regulator
Kp number yes — Potential circuit (voltage) gain coefficient
Ki number yes — Compound circuit (current) gain coefficient
VB_max number yes — Maximum available exciter voltage
Kc number yes — Rectifier loading factor proportional to commutating reactance
Xl number yes — Reactance associated with potential source
thetap number yes — Potential circuit phase angle (degrees)
V_ref number — — Reference voltage set-point

This site uses Just the Docs, a documentation theme for Jekyll.