IEEETurbineGov1
Package: PowerDynamicsOpenAPIModels · Source: Dynamics/DynamicGeneratorComponent/TurbineGov/IEEETurbineGov1.json
IEEE Type 1 Speed-Governing Model
Properties
| Property | Type | Required | Unit | Description |
|---|---|---|---|---|
id | integer | yes | — | Unique integer identifier for this component |
K | integer | yes | — | Governor gain |
T1 | integer | yes | — | Input filter lag |
T2 | number | yes | — | Input filter lead |
T3 | number | yes | — | Valve position time constant |
U0 | number | yes | — | Maximum valve opening rate |
U_c | number | yes | — | Maximum valve closing rate |
valve_position_limits | MinMax | yes | — | Valve position limits |
T4 | number | yes | — | Time constant inlet steam |
K1 | number | yes | — | Fraction of high pressure shaft power |
K2 | number | yes | — | Fraction of low pressure shaft power |
T5 | number | yes | — | Time constant for second boiler pass |
K3 | number | yes | — | Fraction of high pressure shaft power second boiler pass |
K4 | number | yes | — | Fraction of low pressure shaft power second boiler pass |
T6 | number | yes | — | Time constant for third boiler pass |
K5 | number | yes | — | Fraction of high pressure shaft power third boiler pass |
K6 | number | yes | — | Fraction of low pressure shaft power third boiler pass |
T7 | number | yes | — | Time constant for fourth boiler pass |
K7 | number | yes | — | Fraction of high pressure shaft power fourth boiler pass |
K8 | number | yes | — | Fraction of low pressure shaft power fourth boiler pass |
P_ref | number | — | — | Reference power set-point |