ESAC8B

Package: PowerDynamicsOpenAPIModels · Source: Dynamics/DynamicGeneratorComponent/AVR/ESAC8B.json

Excitation System AC8B. Used to represent the Basler Digital Excitation Control System (DECS) with PID controller in PSSE

Properties

Property Type Required Unit Description
id integer yes — Unique integer identifier for this component
Tr number yes — Regulator input filter time constant
Kp number yes — Regulator proportional PID gain
Ki number yes — Regulator integral PID gain
Kd number yes — Regulator derivative PID gain
Td number yes — Regulator derivative PID time constant
Ka number yes — Regulator output gain
Ta number yes — Regulator output lag time constant
Vr_lim MinMax yes — Limits for excitor field voltage
Te number yes — Exciter field time constant
Ke number yes — Exciter field proportional constant
E_sat array of number yes — Exciter output voltage for saturation factor
Se array of number yes — Exciter saturation factor at exciter output voltage
V_ref number — — Reference voltage set-point