ST6B
Package: PowerDynamicsOpenAPIModels · Source: Dynamics/DynamicGeneratorComponent/AVR/ST6B.json
In these excitation systems, voltage (and also current in compounded systems) is transformed to an appropriate level. Rectifiers, either controlled or non-controlled, provide the necessary direct current for the generator field. Parameters of IEEE Std 421.5 Type ST6B Excitacion System. ST6B in PSSE and PSLF
Properties
| Property | Type | Required | Unit | Description |
|---|---|---|---|---|
id | integer | yes | — | Unique integer identifier for this component |
OEL_Flag | integer | yes | — | OEL Flag for ST6B: 1: before HV gate, 2: after HV gate |
Tr | number | yes | — | Regulator input filter time constant |
K_pa | number | yes | — | Regulator proportional gain |
K_ia | number | yes | — | Regulator integral gain |
K_da | number | yes | — | Regulator derivative gain |
T_da | number | yes | — | Voltage regulator derivative channel time constant |
Va_lim | MinMax | yes | — | Regulator output limits |
K_ff | number | yes | — | Pre-control gain of the inner loop field regulator |
K_m | number | yes | — | Forward gain of the inner loop field regulator |
K_ci | number | yes | — | Exciter output current limit adjustment gain |
K_lr | number | yes | — | Exciter output current limiter gain |
I_lr | number | yes | — | Exciter current limiter reference |
Vr_lim | MinMax | yes | — | Voltage regulator limits |
Kg | number | yes | — | Feedback gain constant of the inner loop field regulator |
Tg | number | yes | — | Feedback time constant of the inner loop field voltage regulator |
V_ref | number | — | — | Reference voltage set-point |