VoltageControlAssociation

Package: PowerOperationsOpenAPIModels · Source: Operations/Associations/VoltageControlAssociation.json

Links a voltage control group (a VoltageDroopControl or a ReactivePowerSharing attribute) to one member device and records the member’s relative reactive power weight. One row per (control, member). entity_id names a device that regulates voltage to a setpoint; terminal picks the converter for a two-terminal member (a TwoTerminalVSCLine) and is UNDEFINED for every other member. A device, or a two-terminal line’s converter, belongs to at most one group of either kind. PSS/E RMPCT imports as weight = RMPCT / 100, so the PSS/E default of 100 is the default weight of 1.0.

Properties

Property Type Required Unit Description
control_id integer yes — ID of the VoltageDroopControl or ReactivePowerSharing attribute the member belongs to.
entity_id integer yes — ID of the member device.
weight number — 1 Positive relative weight of this member. Its share of the reactive power required at the regulated bus is weight divided by the sum of the weights of the members in service. Units: 1.
terminal string (VoltageControlTerminal) — — Converter of a two-terminal member this row refers to; required for a TwoTerminalVSCLine member and UNDEFINED for every other member.

This site uses Just the Docs, a documentation theme for Jekyll.