GeneralGovModel

Package: PowerDynamicsOpenAPIModels · Source: Dynamics/DynamicGeneratorComponent/TurbineGov/GeneralGovModel.json

GE General Governor/Turbine Model. The GeneralGovModel (GGOV1) model is a general purpose governor model used for a variety of prime movers controlled by proportional-integral-derivative (PID) governors including gas turbines

Properties

Property Type Required Unit Description
id integer yes — Unique integer identifier for this component
Rselect integer yes — Feedback signal for governor droop
fuel_flag integer yes — Flag switch for fuel source characteristic
R number — — Speed droop parameter
Tpelec number yes — Electrical power transducer time constant
speed_error_signal MinMax yes — Speed error signal limits
Kp_gov number yes — Governor proportional gain
Ki_gov number yes — Governor integral gain
Kd_gov number yes — Governor derivative gain
Td_gov number yes — Governor derivative time constant
valve_position_limits MinMax yes — Valve position limits
T_act number yes — Actuator time constant
K_turb number yes — Turbine gain
Wf_nl number yes — No load fuel flow
Tb number yes — Turbine lag time constant
Tc number yes — Turbine lead time constant
T_eng number yes — Transport lag time constant for diesel engine
Tf_load number yes — Load limiter time constant
Kp_load number yes — Load limiter proportional gain for PI controller
Ki_load number yes — Load integral gain for PI controller
Ld_ref number yes — Load limiter integral gain for PI controller
Dm number yes — Mechanical damping coefficient
R_open number yes — Maximum valve opening rate
R_close number yes — Maximum valve closing rate
Ki_mw number yes — Power controller (reset) gain
A_set number yes — Acceleration limiter setpoint
Ka number yes — Acceleration limiter gain
Ta number yes — Acceleration limiter time constant
T_rate number yes — Turbine rating
db number yes — Speed governor deadband
Tsa number yes — Temperature detection lead time constant
Tsb number yes — Temperature detection lag time constant
R_lim UpDown yes — Maximum rate of load increase
P_ref number — — Reference power set-point

This site uses Just the Docs, a documentation theme for Jekyll.