DEGOV1
Package: PowerDynamicsOpenAPIModels · Source: Dynamics/DynamicGeneratorComponent/TurbineGov/DEGOV1.json
Parameters Woodward Diesel Governor Model. DEGOV1 in PSSE
Properties
| Property | Type | Required | Unit | Description |
|---|---|---|---|---|
id | integer | yes | — | Unique integer identifier for this component |
droop_flag | integer | — | — | Droop control Flag. 0 for throttle feedback and 1 for electric power feedback |
T1 | number | yes | — | Governor mechanism time constant |
T2 | number | yes | — | Turbine power time constant |
T3 | number | yes | — | Turbine exhaust temperature time constant |
K | number | yes | — | Governor gain for actuator |
T4 | number | yes | — | Governor lead time constant |
T5 | number | yes | — | Governor lag time constant |
T6 | number | yes | — | Actuator time constant |
Td | number | yes | — | Engine time delay |
T_lim | array of number | yes | — | Operational control limits on actuator (Tmin, Tmax) |
R | number | yes | — | Steady state droop parameter |
Te | number | yes | — | Power transducer time constant |
P_ref | number | — | — | Reference power set-point |