DEGOV1

Package: PowerDynamicsOpenAPIModels · Source: Dynamics/DynamicGeneratorComponent/TurbineGov/DEGOV1.json

Parameters Woodward Diesel Governor Model. DEGOV1 in PSSE

Properties

Property Type Required Unit Description
id integer yes — Unique integer identifier for this component
droop_flag integer — — Droop control Flag. 0 for throttle feedback and 1 for electric power feedback
T1 number yes — Governor mechanism time constant
T2 number yes — Turbine power time constant
T3 number yes — Turbine exhaust temperature time constant
K number yes — Governor gain for actuator
T4 number yes — Governor lead time constant
T5 number yes — Governor lag time constant
T6 number yes — Actuator time constant
Td number yes — Engine time delay
T_lim array of number yes — Operational control limits on actuator (Tmin, Tmax)
R number yes — Steady state droop parameter
Te number yes — Power transducer time constant
P_ref number — — Reference power set-point