ST8C

Package: PowerDynamicsOpenAPIModels · Source: Dynamics/DynamicGeneratorComponent/AVR/ST8C.json

In these excitation systems, voltage (and also current in compounded systems) is transformed to an appropriate level. Rectifiers, either controlled or non-controlled, provide the necessary direct current for the generator field. Parameters of IEEE Std 421.5 Type ST8C Excitacion System. ST8C in PSSE and PSLF

Properties

Property Type Required Unit Description
id integer yes — Unique integer identifier for this component
OEL_Flag integer yes — OEL Flag for ST8C: <2: Summation at voltage error, 2: OEL takeover at gate
UEL_Flag integer yes — UEL Flag for ST8C: <2: Summation at voltage error, 2: UEL takeover at gate
SCL_Flag integer yes — SCL Flag for ST8C: <2: Summation at voltage error, 2: SCL takeover at UEL and OEL gates
SW1_Flag integer yes — SW1 Flag for power source selector for ST8C: <2: Source from generator terminal voltage, 2: Independent power source
Tr number yes — Regulator input filter time constant
K_pr number yes — Regulator proportional gain
K_ir number yes — Regulator integral gain
Vpi_lim MinMax yes — Regulator input limits
K_pa number yes — Field current regulator proportional gain
K_ia number yes — Field current regulator integral gain
Va_lim MinMax yes — Field current regulator output limits
K_a number yes — Field current regulator proportional gain
T_a number yes — Controlled rectifier bridge equivalent time constant
Vr_lim MinMax yes — Voltage regulator limits
K_f number yes — Exciter field current feedback gain
T_f number yes — Field current feedback time constant
K_c1 number yes — Rectifier loading factor proportional to commutating reactance
K_p number yes — Potential circuit (voltage) gain coefficient
K_i1 number yes — Potential circuit (current) gain coefficient
X_l number yes — Reactance associated with potential source
theta_p number yes — Potential circuit phase angle (degrees)
VB1_max number yes — Maximum available exciter voltage
K_c2 number yes — Rectifier loading factor proportional to commutating reactance
K_i2 number yes — Potential circuit (current) gain coefficient
VB2_max number yes — Maximum available exciter voltage
V_ref number — — Reference voltage set-point
Ifd_ref number — — Reference field current set-point

This site uses Just the Docs, a documentation theme for Jekyll.