SalientPoleMachine

Package: PowerDynamicsOpenAPIModels · Source: Dynamics/DynamicGeneratorComponent/Machine/SalientPoleMachine.json

Parameters of 3-states salient-pole synchronous machine with quadratic/exponential saturation: IEEE Std 1110 §5.3.1 (Model 2.1). GENSAL or GENSAE model in PSSE and PSLF

Properties

Property Type Required Unit Description
id integer yes — Unique integer identifier for this component
R number yes — Armature resistance
Td0_p number yes s Time constant of transient d-axis voltage Units: s.
Td0_pp number yes s Time constant of sub-transient d-axis voltage Units: s.
Tq0_pp number yes s Time constant of sub-transient q-axis voltage Units: s.
Xd number yes — Reactance after EMF in d-axis
Xq number yes — Reactance after EMF in q-axis
Xd_p number yes — Transient reactance after EMF in d-axis
Xd_pp number yes — Sub-Transient reactance after EMF in d-axis. Note: Xd_pp = Xq_pp
Xl number yes — Stator leakage reactance
Se array of number yes — Saturation factor at 1 and 1.2 pu flux: Se(eqp) = B(eqp-A)^2

This site uses Just the Docs, a documentation theme for Jekyll.