SalientPoleMachine
Package: PowerDynamicsOpenAPIModels · Source: Dynamics/DynamicGeneratorComponent/Machine/SalientPoleMachine.json
Parameters of 3-states salient-pole synchronous machine with quadratic/exponential saturation: IEEE Std 1110 §5.3.1 (Model 2.1). GENSAL or GENSAE model in PSSE and PSLF
Properties
| Property | Type | Required | Unit | Description |
|---|---|---|---|---|
id | integer | yes | — | Unique integer identifier for this component |
R | number | yes | — | Armature resistance |
Td0_p | number | yes | s | Time constant of transient d-axis voltage Units: s. |
Td0_pp | number | yes | s | Time constant of sub-transient d-axis voltage Units: s. |
Tq0_pp | number | yes | s | Time constant of sub-transient q-axis voltage Units: s. |
Xd | number | yes | — | Reactance after EMF in d-axis |
Xq | number | yes | — | Reactance after EMF in q-axis |
Xd_p | number | yes | — | Transient reactance after EMF in d-axis |
Xd_pp | number | yes | — | Sub-Transient reactance after EMF in d-axis. Note: Xd_pp = Xq_pp |
Xl | number | yes | — | Stator leakage reactance |
Se | array of number | yes | — | Saturation factor at 1 and 1.2 pu flux: Se(eqp) = B(eqp-A)^2 |