EXAC2

Package: PowerDynamicsOpenAPIModels · Source: Dynamics/DynamicGeneratorComponent/AVR/EXAC2.json

Modified AC2. This excitation systems consists of an alternator main exciter feeding its output via non-controlled rectifiers. The exciter does not employ self-excitation, and the voltage regulator power is taken from a source that is not affected by external transients. Parameters of IEEE Std 421.5 Type AC2A Excitacion System. The alternator main exciter is used, feeding its output via non-controlled rectifiers. The Type AC2C model is similar to that of Type AC1C except for the inclusion of exciter time constant compensation and exciter field current limiting elements. EXAC2 in PSSE and PSLF

Properties

Property Type Required Unit Description
id integer yes — Unique integer identifier for this component
Tr number yes — Regulator input filter time constant
Tb number yes — Regulator denominator (lag) time constant
Tc number yes — Regulator numerator (lead) time constant
Ka number yes — Regulator output gain
Ta number yes — Regulator output time constant
Va_lim MinMax yes — Limits for regulator output
Kb number yes — Second stage regulator gain
Vr_lim MinMax yes — Limits for exciter field voltage
Te number yes — Exciter field time constant
Kl number yes — Exciter field current limiter gain
Kh number yes — Exciter field current regulator feedback gain
Kf number yes — Rate feedback excitation system stabilizer gain
Tf number yes — Rate feedback time constant
Kc number yes — Rectifier loading factor proportional to commutating reactance
Kd number yes — Demagnetizing factor, function of exciter alternator reactances
Ke number yes — Exciter field proportional constant
V_lr number yes — Maximum exciter field current
E_sat array of number yes — Exciter output voltage for saturation factor
Se array of number yes — Exciter saturation factor at exciter output voltage
V_ref number — — Reference voltage set-point

This site uses Just the Docs, a documentation theme for Jekyll.