Read Component Values in Different Unit Systems

PowerSystems.jl stores component parameters internally in per-unit on the device base, but getter functions automatically convert values to whatever unit system the System is currently set to. This page shows how to switch unit systems and interpret the results.

For background on why PowerSystems.jl uses per-unit conventions and what each unit system means, see Per-unit Conventions.

Step 1: Check or change the unit system

Use get_units_base to check the current setting and set_units_base_system! to change it:

using PowerSystems

# Build a minimal system with one bus and one generator.
bus = ACBus(;
    number = 1,
    name = "bus1",
    available = true,
    bustype = ACBusTypes.REF,
    angle = 0.0,
    magnitude = 1.0,
    voltage_limits = (min = 0.9, max = 1.05),
    base_voltage = 230.0,
)

sys = System(100.0)  # System base power = 100 MVA
add_component!(sys, bus)

get_units_base(sys)  # Returns the current unit system, e.g. "SYSTEM_BASE"

set_units_base_system!(sys, "NATURAL_UNITS")
[ Info: Unit System changed to UnitSystem.NATURAL_UNITS = 2

The three supported options are:

SettingMeaning
"SYSTEM_BASE"Values divided by the system base_power (default)
"DEVICE_BASE"Values divided by the device's own base_power
"NATURAL_UNITS"Values in physical units (MW, MVA, etc.)

Step 2: Read values with getter functions

Once the unit system is set, all getter functions return values in the corresponding units:

# Add a 100 MVA thermal generator to the system created in Step 1.
gen = ThermalStandard(;
    name = "gen1",
    available = true,
    status = true,
    bus = bus,
    active_power = 0.0,
    reactive_power = 0.0,
    rating = 1.0,                                   # 1.0 p.u. on device base = 100 MVA
    active_power_limits = (min = 0.2, max = 1.0),   # p.u. on device base
    reactive_power_limits = nothing,
    ramp_limits = nothing,
    operation_cost = ThermalGenerationCost(nothing),
    base_power = 100.0,                             # MVA — always stored in natural units
    prime_mover_type = PrimeMovers.CC,
    fuel = ThermalFuels.NATURAL_GAS,
)
add_component!(sys, gen)

# In DEVICE_BASE
set_units_base_system!(sys, "DEVICE_BASE")
get_base_power(gen)           # Returns: 100.0 MVA (always natural units)
get_rating(gen)               # Returns: 1.0 p.u. (on device base)
get_max_active_power(gen)     # Returns: 1.0 p.u. (on device base)

# In NATURAL_UNITS
set_units_base_system!(sys, "NATURAL_UNITS")
get_base_power(gen)           # Returns: 100.0 MVA (always natural units)
get_rating(gen)               # Returns: 100.0 MVA (converted from device p.u.)
get_max_active_power(gen)     # Returns: 100.0 MW (converted from device p.u.)

# In SYSTEM_BASE
set_units_base_system!(sys, "SYSTEM_BASE")
get_base_power(gen)           # Returns: 100.0 MVA (always natural units)
get_rating(gen)               # Returns: 1.0 p.u. (on system base, when system base = device base)
get_max_active_power(gen)     # Returns: 1.0 p.u. (on system base)
1.0
Note

get_base_power always returns a value in natural units (MVA) regardless of the unit system setting. Only parameters such as rating and max_active_power are affected by the unit system.

Using a context manager to avoid permanent changes

If you only need values in a particular unit system temporarily, use with_units_base instead of set_units_base_system!. It restores the original unit system automatically after the block completes, even if an error occurs:

mw_value = with_units_base(sys, "NATURAL_UNITS") do
    get_max_active_power(gen)
end
# Unit system is restored to its previous value here
100.0

See Use Context Managers for Efficient Bulk Operations for more examples.